Single Phase Motor Full Load Amps Table


Full Load Amperes
Horsepower115 V208 V230 VMinimum
Transformer
KVA
1/64.42.42.2.53
1/45.83.22.9.70
1/37.24.03.6.87
1/29.85.44.91.18
3/413.87.66.91.66
1168.881.92
1-1/22011102.40
22413.2122.88
33418.7174.10
55630.8286.72
7-1/28044409.6
10100555012

(1) When motor service factor is greater than 1, increase full load amps proportionally.
Example: If service factor is 1.15, increase above amp values by 15%.
Note: If motors are started more than once per hour add 20% additional KVA. (Table by Acme Electric Corporation).