Three Phase Motor Full Load Amps Table


Full Load Amperes
Horsepower208 V230 V460 V575 VMinimum
Transformer
KVA
1/22.22.01.00.80.9
3/43.12.81.41.11.2
14.03.61.81.41.5
1-1/25.75.22.62.12.1
27.56.83.42.72.7
310.79.64.83.93.8
516.715.27.66.16.3
7-1/224221199.2
103128141111.2
154642211716.6
205954272221.6
257568342726.6
308880403232.4
40114104524143.2
50143130655252
60170154776264
75211192967780
10027324812499103
125342312156125130
150396360180144150
200528480240192200

(1) When motor service factor is greater than 1, increase full load amps proportionally.
Example: If service factor is 1.15, increase above amp values by 15%.
Note: If motors are started more than once per hour add 20% additional KVA. (Table by Acme Electric Corporation).