Principio de la página

Service Equipment Grounding Table


Table 250.66 Grounding Electrode Conductor
for Alternating-Current System
Size of Largest Ungrounded
Service-Entrance Conductor
or Equivalent Area for
Parrell Conductorsa
(AWG/kcmil)
Size of Grounding
Electrode Conductor
(AWG/kcmil)
CopperAluminum or
Copper-Clad
Aluminum
CopperAluminum or
Copper-Clad
Aluminum
2 or smaller1 or smaller86
1 or 1/02/0 or 3/064
2/0 or 3/04/0 or 25042
Over 3/0
through 350
Over 250
through 500
21/0
Over 350
through 600
Over 500
through 900
1/03/0
Over 600
through 1100
Over 900
through 1750
2/04/0
Over 1100Over 17503/0250

Notes:
1. Where multiple sets of service-entrance conductors are used as permitted in 230.40, Exception No.2, the equivalent size of the largest service-entrance conductor shall be determined by the largest sum of the areas of the corresponding conductors of each set.
2. Where there are no service-entrance conductors, the grounding electrode conductor size shall be determined by the equivalent size of the largest service-entrance conductor required for the load to be served.

aThis table also applies to the derived conductors of separately derived ac systems.
bSee installation restrictions in Section 250-64(A).

Service Equipment Grounding Table


Table 250.66 Grounding Electrode Conductor
for Alternating-Current System
Size of Largest Ungrounded
Service-Entrance Conductor
or Equivalent Area for
Parrell Conductorsa
(AWG/kcmil)
Size of Grounding
Electrode Conductor
(AWG/kcmil)
CopperAluminum or
Copper-Clad
Aluminum
CopperAluminum or
Copper-Clad
Aluminum
2 or smaller1 or smaller86
1 or 1/02/0 or 3/064
2/0 or 3/04/0 or 25042
Over 3/0
through 350
Over 250
through 500
21/0
Over 350
through 600
Over 500
through 900
1/03/0
Over 600
through 1100
Over 900
through 1750
2/04/0
Over 1100Over 17503/0250

Notes:
1. Where multiple sets of service-entrance conductors are used as permitted in 230.40, Exception No.2, the equivalent size of the largest service-entrance conductor shall be determined by the largest sum of the areas of the corresponding conductors of each set.
2. Where there are no service-entrance conductors, the grounding electrode conductor size shall be determined by the equivalent size of the largest service-entrance conductor required for the load to be served.

aThis table also applies to the derived conductors of separately derived ac systems.
bSee installation restrictions in Section 250-64(A).