Three Phase Transformer Full Load Amps Table


3 Phase KVA =Volts x Amps x 1.73
1000
KVA208v240v480v600v
38.37.23.62.9
616.614.47.25.8
92521.610.88.6
1541361814.4
2262542721.6
3083723628
451241085443
752081809072
112-1/2312270135108
150416360180144
225624541270216
300832721360268
50013871202601481
75020841806903723

*When motor service factor is greater than 1, increase full load amps proportionally. Example: If service factor is 1.15, increase above amp values by 15%.